logo

CPU-1 refrigerant detector in aluminum case

Product: 04-545-8501
Call us for a price

CPU-1 refrigerant detector in aluminum case

An advanced microprocessor is the heart of this unit. Its digital processing permits better management of circuitry and sensing tip signal than ever before possible. Additionally, the number of components used in the circuit is reduced nearly 40%, increasing reliability and performance. The microprocessor monitors the sensing tip and battery voltage levels 4000 times per second. Compensating for even the most minor fluctuations in signal. This translates into stable and dependable tool in almost any environment.
Convenience features have been added to enhance the usability of the CPU-1G. Seven levels of sensitivity provide an increase of 64 times from level 1 to level 7. Unique Tri-Color LED's show a progressive and wide ranging leak size indication, communicate the sensitivity level, and provide a true voltage indication of battery power level. A tactile keypad controls all functions of operation. A revolutionary new case design gives the user grip a control, and places the visual indicators in direct sight during use.

Features:
Microprocessor control, with advanced digital signal processing 
Tricolor visual display
Seven levels of sensitivity provide an increase of up to 64
Tactile keypad controls
Real time sensitivity adjustment
Battery test function
Battery voltage indication
Detect ALL halogen refrigerants
True mechanical pumping provides positive airflow through sensing tip
Mute feature included
Cordless and portable, operates on 2 cell batteries
Carrying case included
Flexible and stainless probe
Optional carrying holster
Optional reference leak source
Two-year warranty

Applications:
The CPU-1G leak detector may also used to:

Detect leaks in other systems and storage/recovery containers. It will respond to ALL halogenated (contains Chlorine of Fluorine) refrigerants. This includes, but is not limited to:
CFCs e.g. R12, R11, R500, R503 etc
HCFCs e.g.R22, R123, R502 etc
HFCs e.g.R134a, R404a, R125 etc
Blends such as AZ-50 HP62 MP39 etc
Detect ethylene oxide gas leaks in hospital sterilizing equipment (it will detect the halogenated carrier gas)
Detect SF-6 in high voltage circuit breakers
Detect most gases that contain Chlorine, Fluorine, and Bromine (halogen gases)
Detect cleaning agents used in dry cleaning applications such as erchloroethyl.
Specifications

Power supply: 3V DC, two cell Alkaline batteries 
Maximum sensitivity: R12,R22,R134a,0.5 oz/yr (14g/yr) 
Ultimate sensitivity: less than 0.1 oz/yr (3g/yr) for all halogen based refrigerants 
Sensing tip life: approx. 20hours 
Operating temperature: 30?to 125?(0? to 52?) 
Battery life: approximately 30 hours in normal use 
Duty cycle: continuous, no limitation 
Response time: two second 
Warm-up time: approximately 6 seconds 
Unit weight: 560 grams 
Unit dimensions: 22.9 6.5 6.5cm 
Fixed probe length: 35.5cm 
Gross Weight: 1600G/PC 
Packing: 8 PCS/CTN 
Measurement of the carton: 57×36×39cm






INFORMATION

piraeusbank verisign verified_by_visa verified_by_visa paypal
logo-bottom
1st Branch: 5 St. Tatti st. P.C. 54622
(Ag. sofias area) Thessaloniki - Greece
t. +30 2310 236321, +30 2310 267168
f. +30 2310 281007
2nd Branch: 6th Klm. Lagkada road (Towards Oreokastro)
P.O. Box 40052 Thessaloniki - Greece
t. +30 2310 681123, +30 2310 685510, 2310 685511
f. +30 2310 684701
Login-iconLogin